Protection Coordination

Interactive calculator

Evaluate and set protective device coordination for overcurrent and ground fault protection in power systems.

Verify coordination between devices.

๐Ÿ“ฅ Input Parameters

๐Ÿ“ Calculation Steps

1

Identify fault levels

From short-circuit study

Maximum and minimum fault current at each bus.

2

Plot TCC curves

Per manufacturer curves

Time-current characteristics on log-log scale.

3

Check selectivity

t_feeder + 0.1s < t_main for all I_f

Verify no time overlap at any fault level.

4

Arc flash review

E proportional to t_clear

Evaluate if decreased trip delay reduces arc flash energy.

๐Ÿงฎ Formula

Selectivity & TCC Analysis

t_feeder + margin < t_main at all fault levels; selectivity ratio = t_main/t_feeder > 1.5

Coordinated device operation ensures selective fault isolation.

SymbolVariableUnitDescription
I_f Fault current kA
t_main Main device trip time s
t_feeder Feeder device trip time s
margin Selectivity margin s

๐Ÿ“‹ Worked Example: 480V Switchboard Selectivity

Result:

๐Ÿ” Result Interpretation

โœ… Margin > 0.2s
โœ… 0.1-0.2s
โœ… < 0.1s

๐Ÿ”ฅ Guidance

Coordination failure Margin < 0.1s at critical fault

Device miscoordination can cause wide-area outages.

๐Ÿ’ก Engineering Recommendations

๐Ÿ”ง

Arc flash > 8 cal/cm2 at downstream gear

Implement maintenance switch or zone interlocking.

Maintenance switch reduces main breaker delay to instantaneous during energized work.

โšก Quick Facts

Current-based, time-based, energy-based, zone interlocking
Selectivity types
Distribution required selective per 240.12
NEC requirement
Faster trip = less energy, but may lose selectivity
Arc flash trade-off

๐Ÿ”ฌ Engineering Insight

"The designer's challenge is balancing selectivity with arc flash energy. Modern approaches use zone-selective interlocking (ZSI): fast trip for downstream faults (lower arc flash) while maintaining selectivity through signaling between devices."

๐Ÿ“œ Standards & References

IEEE 242-2001 โ€” IEEE

Protection and coordination of industrial power systems.

โ†—
NEC 240.12 โ€” NFPA

Electrical system coordination requirements.

โ†—